Question

How do you prioritize API 653 inspection recommendations?

API 653 does not define a priority-code scheme. Clause 6.9.3.1 requires the report to recommend the repairs and monitoring needed to restore the tank’s integrity, or keep it until the next inspection, with the reason for each, and clause 6.9.3.2 makes the owner/operator responsible for setting the repair scope and timing. So the priority labels come from the owner’s inspection program; the inspector writes each recommendation so it can be placed in that scheme.

Required repairs vs other recommendations

Clause 6.9.3.1 separates two kinds. Recommendations for repairs and monitoring needed to restore integrity under the standard, or to keep it until the next inspection, are required, each with its reason. The report may also include other, less critical observations and suggestions. Keep the two apart in the report so a required repair never reads like a suggestion. The report also states the recommended maximum inspection interval and how it was calculated, and the repair and corrosion mitigation the next internal interval depends on (clause 6.9.2 k).

What a recommendation should hold

  • The finding: what was found, with the measured value.
  • The location: plate, course, nozzle or station, matching the drawing.
  • The basis: the API 653 clause or limit it fails or approaches.
  • The action: repair, monitor, evaluate or re-inspect, in plain words.
  • The timing: when it needs to be done, in the owner’s terms.

Timing: what API 653 gives you

Clause 6.9.3.2 lists typical timing, which most programs build on:

  • Before the tank returns to service: repairs critical to integrity, such as bottom or shell repairs.
  • After return to service: minor repairs and maintenance, such as drainage, painting, gauge repairs or grouting.
  • At the next scheduled internal inspection: predicted repairs and maintenance, such as coating renewal or planned bottom repairs.
  • Monitor: conditions to watch, such as roof or shell corrosion or settlement.

An example scheme (example only; use the owner’s)

Owners use their own codes and timeframes. When the owner has a scheme, use it exactly, and do not mix in a second one. Where none exists yet, a simple four-level scheme looks like this:

  • A: before return to service. Required for integrity under API 653.
  • B: within a set time after return to service, as the owner’s program defines.
  • C: at or before the next scheduled internal inspection.
  • D: monitor at routine and external inspections; no repair yet.

After the report

The owner/operator must document the disposition of every recommended repair and monitoring item in writing, with reasons if an action is delayed or judged unnecessary (clause 6.9.3.2). Reports, recommendations and dispositions are kept for the life of the tank (clause 6.9.1).

Also asked as

How do you write tank inspection recommendations?

One recommendation per finding, each with the measured value, the location, the API 653 basis, the action and the timing, plus the reason for it as clause 6.9.3.1 requires.

Does API 653 have a repair priority system?

No. Clause 6.9.3.2 gives typical timing (before return to service, after return to service, at the next internal inspection, monitor) and leaves the scope and timing to the owner/operator. Priority codes come from the owner’s program.

Mandatory vs recommended repairs: what is the difference?

Repairs and monitoring needed to restore integrity under API 653, or to keep it until the next inspection, must be recommended with reasons (clause 6.9.3.1). Less critical observations and suggestions may be added. The owner/operator decides the timing and documents the disposition of each.

TankForge is API 653 inspection software built by a working API 653 inspector. Draft report. Your certified inspector reviews and signs.